Product Description


Product Overview


According to the GB/T18802.1-2011 standard, the front end of the SPD circuit must be connected in series with the overcurrent protection appliance required by the surge protector manufacturer. Because the current fuses and miniature circuit breakers cannot be coordinated with SPD, when the power supply is abnormal or the SPD is deteriorated and fails, the fire and equipment damage caused by lightning strikes have seriously affected the normal production and operation!
At present, the miniature circuit breakers used with SPD masters cannot be matched with the following 4 points.1. The lightning current impact is very easy to damage. The lightning protection fails, 2. The lightning surge current residual voltage is high. The reliability of the lightning protection of the equipment is reduced; 3. Power frequency continuous current does not trip, a power supply abnormal SPD fires; 4. Lightning shock accidentally trips and lightning protection fails.


Functions and scope of application


The SPD special external detach is connected in series on the SPD return path, and the internal current separation channel device is used to achieve a low-current speed cut with high current and lightning shock. To achieve the protection of small power current SPD fire protection, lightning impact SPD continuous protection role, SCB products limit the use of thousands of SPD back pass current protection, or backup current protection should not be used in other occasions.


Product characteristics


1, participate in the control of the outlet mechanism, selective separation through the current;
2, impact current residual low, can be with the fuse United States;
3, high-energy contacts, long service life;
4, small broken shape volume, convenient power off the SPD for testing;
5, full specifications, meet in Tl, T2, T3 SPD supporting;
6, 35mm CLIP rail installation, meet the needs of installation around the world.
P43

The main technical parameters


Model Specifications

LTSCB-40

LTSCB-80

LTSCB-15

No unbuckling impact current Le

≤40kA(8/20μs)

≤80kA(8/20μs)

≤15kA(10/350μs)

Standards compliant

Meet GB/T18802.1-2011 test standards

Rated operating voltage Uopv

230VAC

Rated insulation voltage Ui

400VAC

Current detach value lo

3A

Running short circuit capability LCS

6KA/20KA

20KA/40KA

50KA/100KA

Short circuit current separation time Tcs

≤40ms

Load current separation time to

≤50ms

Electrical life

>1000次

Shell Protection Level

Ip20

Minimum area of connection cable

2.5mm2/1exible

Maximum area of connection cable

25mm2/1exible

Shell Material

PA66 UL94V-0

ShapeSize

Pa6691x73x17.8mm

work environment

Temperature:-40C~75C Considerable humidity:95%(25°C)

ShellColor

Shell:greenhandle:Orange

InstallCLIPrail

EN60715(35mm)


Typical application/Shape dimensions