Loading...

LT-Ⅰ12.5/4P

Product Description


Product Overview


LT1 voltage switch type series one-stage modular power supply surge protector based on! EC and GB standard design. Applied to the first-stage protection of the power supply system, the product is a standard 35mm guide rail installation method.
The LT1 voltage switch series modular power supply surge protector has a high lightning current discharge capability, and the single module impact current can reach a maximum of 50 kA(10/350us), which can prevent various electric surges including direct strikes.The first-stage power surge protection of the power supply system applied to the equipment system with high lightning strike risk can be combined for single-phase and three-phase substitution lines.


Product structure and performance characteristics


This product is an indoor fixed installation voltage switch type SPD, which is designed in accordance with current national standards such as GB/T18802.1; it has the advantages of large inrush current (limp:25KA) and low residual voltage (up:2.0KV) Its core components are composed of multi-level graphite gaps. Reasonable design and precise machining combine the spark gaps to form a sealed structure to ensure the safe distance inside the spark gap, even when surge current passes through, it will not produce There is no need to reserve space for arc leakage during installation. The quality is stable and reliable.
The product is installed at the junction of LPZOA or LPZOB and LPZ1, or at the main distribution box (cabinet) where the power is introduced, using 35mm standard guide rails. The connecting guide rail adopts 6-35mm2 multi-strand copper flexible wire.
The grounding wire should be a two-color wire of 16mm2 or more, and the length should not be greater than 500mm. In order to prevent the failure of the surge protector from affecting the normal operation of the power grid, the protector connected to the L line should be connected in series with a fuse or circuit breaker (note:select according to the nominal current In)。

Technical Parameter


Model Specifications

LT-I15

LT-125

LT-150

Rated operating voltage Uopv

220V

220V

220V

Maximum continuous operating voltage Uc(VAC)

385V

385V

385V

Voltage protection level Up(k V)5

0≤2.2KV

0≤2.4KV

0≤2.5KV

Maximum discharge current(8/20 us)LMAX(kA)

15KA

25KA

50KA

Nominal discharge current(8/20 us)ln(kA)

40KA

50KA

100KA

Response time NS

≤100ns

≤100ns

≤100ns

Protection Level

IP20

IP20

IP20

The front end recommends a series fuse

125A

150A

150A

Access conductor cross-sectional area(mm2

≥6mm2


Grounding line cross-sectional area(mm2

≥10mm2


Telephony function

Optional


Remarks

其他最大持续工作电压UC可定做(500V,690V)



Diagram/Shape dimensions






Online Inquiry

Related Products

See More